Browse catalog

Taco / HVAC / Low Water Cutoff

Taco LFM12031-1

Primary role is an HVAC boiler limit control; alarm and water-feeder outputs are secondary interfaces.

Open manufacturer PDFView My List
Device specifications
FieldValue
Product TypeFoam-compensating low water cutoff
Reset TypeManual
Input Power120 V AC
Process Connection3/4 in NPT
Probe Style12 in long electrode, remote NEMA 4 style
Maximum PressureSteam or hot water: 250 PSI
Maximum Probe Temperature250°F (121°C)
Maximum Ambient Temperature150°F (66°C)
Probe SensitivityExtended operation to 20 kΩ; service range 20-40 kΩ
Contact Rating7.5 A full load / 43.2 A locked rotor; 125 VA pilot duty at 120 V AC
ListingsUL 353; CSA C22.2 No. 205; FM approved; CSD-1 compliant
Est. Year Mfr2009

Refer to the manufacturer documentation for installation requirements and current product information.