Device specifications
FieldValue
Product TypeFoam-compensating low water cutoff
Reset TypeManual
Input Power24 V AC, external Class 2 source
Process Connection1/2 in NPT
Probe StyleStandard
Maximum PressureSteam or hot water: 250 PSI
Maximum Probe Temperature250°F (121°C)
Maximum Ambient Temperature150°F (66°C)
Probe SensitivityExtended operation to 20 kΩ; service range 20-40 kΩ
Contact Rating50 VA pilot duty at 24 V AC
ListingsUL 353; CSA C22.2 No. 205; FM approved; CSD-1 compliant
Est. Year Mfr2009