Browse catalog

Siemens / HVAC / Thermostat

Siemens 134-1504

Open manufacturer PDFView My List
Device specifications
FieldValue
Product TypeLow-temperature cut-out and alarm thermostat
Switch ActionMain and reverse-acting auxiliary contacts
Range35–45 °F (2–7 °C)
Minimum Differential5 °F (2.8 °C), non-adjustable
Maximum Bulb Temperature250 °F (121 °C)
Ambient Temperature0–140 °F (-18–60 °C)
Sensing ElementVapor filled
Est. Year Mfr2005