Browse catalog

Siemens / HVAC / Sensor

Siemens QRA4.U

Industrial burner flame supervision; not a fire-alarm detector.

Open manufacturer PDFView My List
Device specifications
FieldValue
Product TypeUV flame detector for gas or oil burners
Spectral Range190–270 nm
UV Cell LifeApprox. 10,000 h at max. 50 °C
Combustion Chamber Pressure150 mbar maximum
ProtectionIP54 when mounted
Operating Temperature-20 to 60 °C
Humidity<95% RH
Connecting WiresApprox. 1.8 m
Mounting Thread3/4-14 NPSM
WeightApprox. 180 g
Est. Year Mfr2008

Refer to the manufacturer documentation for installation requirements and current product information.