Browse catalog

Schneider Electric / Power / UPS

Schneider Electric Easy UPS 3L

Open manufacturer PDFView My List
Device specifications
FieldValue
UPS TypeThree-phase double-conversion UPS
Power RangeCatalog series range: 10 to 600 kVA
Phase Configuration3:1 from 10 to 30 kVA; 3:3 from 10 to 600 kVA
Input Voltage380 / 400 / 415 V
Input Frequency45 to 65 Hz
Input Power Factor>0.99
Online EfficiencyUp to 96%
ECO EfficiencyUp to 99%
Output Regulation±1%
CommunicationsRS-232, RS-485, USB, dry contacts, and Modbus TCP; optional network card
Est. Year Mfr2021

Refer to the manufacturer documentation for installation requirements and current product information.