Potter / Building Automation / Pressure Switch

Potter ADPS-300-IB

Primary role is a general operating pressure control for pumps and compressors; sprinkler-system cautions are incidental.

Open manufacturer PDFView My List
Device specifications
FieldValue
Switch TypeAdjustable deadband pressure switch
Stock Number1370010
Operating Range25-300 PSIG
Minimum Deadband12 PSIG at mid-range
Proof Pressure400 PSIG
Factory Setting90/60 PSIG
Pressure Connection1/4-18 NPT female; optional 3/8-18 NPT female
Switch ContactSPDT Form C; 15 A at 125 V AC; 8 A at 250 V AC
MediaAir, water, or compatible non-hazardous fluid
EnclosureNEMA Type 4X (IP66), indoor/outdoor
Ambient/Media Temperature-4°F to 180°F (-20°C to 82°C)
Est. Year Mfr2016